Saturday, November 20, 2010

Panasonic Fault Diagnostics – Older Style FS Units R22


Fault Diagnostics – Older Style FS Units R22
First generation series 11NP Series with E style fault codes
Press check on the Wired Controller to call up the Fault Codes.

Fault Code At Remote  = E1
Indoor Unit PCB
LED1   = Flash
LED2   = Flash
LED3   = Flash
Measuring Of Fault Code = Signal from RC to ID Unit faulty

Fault Code At Remote  = E2
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
Measuring Of Fault Code = Float Switch

Fault Code At Remote  = E3
Indoor Unit PCB
LED1   =
LED2   = Lit
LED3   = 
Measuring Of Fault Code = Air Sensor Faulty

Fault Code At Remote  = E4
Indoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
Measuring Of Fault Code = Pipe sensor Faulty

Second Generation 21NP Series with F Fault Codes
Press Check on the Wired Controller to call up the Fault Codes

Fault Code At Remote  = F2
Indoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   =
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Float switch

Fault Code At Remote  = F3
Indoor Unit PCB
LED1   =
LED2   = Lit
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Indoor Air Sensor Faulty

Fault Code At Remote  = F4
Indoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Indoor Air Sensor Faulty

Fault Code At Remote  = F5
Indoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   = Lit
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Signal from RC to ID faulty

Fault Code At Remote  = F5
Indoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = No Signal from ID to RC

Fault Code At Remote  = F6
Indoor Unit PCB
LED1   =
LED2   = Lit
LED3   = Lit
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Signal from ID to OD faulty

Fault Code At Remote  = F6
Indoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = No Signal from Od to ID

Fault Code At Remote  = F13
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   = Lit
Measuring Of Fault Code = OD Unit Overcurrent Protection

Fault Code At Remote  = F15
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   =
LED4   =
Measuring Of Fault Code = HP Switch

Fault Code At Remote  = F18
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   = Lit
LED4   =
Outdoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
LED4   =
Measuring Of Fault Code = Outdoor Pipe Sensor Faulty


Kindly Bookmark this Post using your favorite Bookmarking service: