Fault Diagnostics – Older Style FS Units R22
First generation series 11NP Series with E style fault codes
Press check on the Wired Controller to call up the Fault Codes.
Fault Code At Remote = E1
Indoor Unit PCB
LED1 = Flash
LED2 = Flash
LED3 = Flash
Measuring Of Fault Code = Signal from RC to ID Unit faulty
Fault Code At Remote = E2
Indoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
Measuring Of Fault Code = Float Switch
Fault Code At Remote = E3
Indoor Unit PCB
LED1 =
LED2 = Lit
LED3 =
Measuring Of Fault Code = Air Sensor Faulty
Fault Code At Remote = E4
Indoor Unit PCB
LED1 =
LED2 =
LED3 = Lit
Measuring Of Fault Code = Pipe sensor Faulty
Second Generation 21NP Series with F Fault Codes
Press Check on the Wired Controller to call up the Fault Codes
Fault Code At Remote = F2
Indoor Unit PCB
LED1 = Lit
LED2 = Lit
LED3 =
LED4 = Lit
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = Float switch
Fault Code At Remote = F3
Indoor Unit PCB
LED1 =
LED2 = Lit
LED3 =
LED4 =
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = Indoor Air Sensor Faulty
Fault Code At Remote = F4
Indoor Unit PCB
LED1 =
LED2 =
LED3 = Lit
LED4 =
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = Indoor Air Sensor Faulty
Fault Code At Remote = F5
Indoor Unit PCB
LED1 = Lit
LED2 = Lit
LED3 = Lit
LED4 = Lit
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = Signal from RC to ID faulty
Fault Code At Remote = F5
Indoor Unit PCB
LED1 = Lit
LED2 = Lit
LED3 =
LED4 =
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = No Signal from ID to RC
Fault Code At Remote = F6
Indoor Unit PCB
LED1 =
LED2 = Lit
LED3 = Lit
LED4 = Lit
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = Signal from ID to OD faulty
Fault Code At Remote = F6
Indoor Unit PCB
LED1 =
LED2 =
LED3 = Lit
LED4 = Lit
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Measuring Of Fault Code = No Signal from Od to ID
Fault Code At Remote = F13
Indoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Outdoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 = Lit
Measuring Of Fault Code = OD Unit Overcurrent Protection
Fault Code At Remote = F15
Indoor Unit PCB
LED1 = Lit
LED2 =
LED3 =
LED4 =
Outdoor Unit PCB
LED1 = Lit
LED2 = Lit
LED3 =
LED4 =
Measuring Of Fault Code = HP Switch
Fault Code At Remote = F18
Indoor Unit PCB
LED1 = Lit
LED2 =
LED3 = Lit
LED4 =
Outdoor Unit PCB
LED1 =
LED2 =
LED3 = Lit
LED4 =
Measuring Of Fault Code = Outdoor Pipe Sensor Faulty