Tuesday, November 9, 2010

Mr Slim A-Control Check Code (E Indication)


INDICATIONS ON REMOTE CONTROL = E0
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Remote Control
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave been performed?
2) Is a specified 2 core wire used for the electric wire? (03 - 1.25mm2 ) A wire with 3 or more cores is NG

INDICATIONS ON REMOTE CONTROL = E3
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Remote Control
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave been performed?
2) Is a specified 2 core wire used for the electric wire? (03 - 1.25mm2 ) A wire with 3 or more cores is NG


INDICATIONS ON REMOTE CONTROL = E4
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave been performed?
2) Is a specified 2 core wire used for the electric wire? (03 - 1.25mm2 ) A wire with 3 or more cores is NG


INDICATIONS ON REMOTE CONTROL = E5
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave been performed?
2) Is a specified 2 core wire used for the electric wire? (03 - 1.25mm2 ) A wire with 3 or more cores is NG


INDICATIONS ON REMOTE CONTROL = E6
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice

LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated

INDICATIONS ON REMOTE CONTROL = E7
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated

INDICATIONS ON REMOTE CONTROL = E8
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated

INDICATIONS ON REMOTE CONTROL = E9
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated

INDICATIONS ON REMOTE CONTROL = EA
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Once
FAULTS = Wiring for connection between indoor unit and outdoor unit is wrong
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated

INDICATIONS ON REMOTE CONTROL = Eb
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Once
FAULTS = Wiring for connection between indoor unit and outdoor unit is wrong (improper or seperated)
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated

INDICATIONS ON REMOTE CONTROL = EE
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 4 times
FAULTS = The combination is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor unit and Outdoor unit
THE PART TO BE CHECKED = 1) Check the combination of indoor unit and outdoor unit

INDICATIONS ON REMOTE CONTROL = EF
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 4 times
FAULTS = Non-definition error (M-NET system error / No target code)
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor unit and Outdoor unit
THE PART TO BE CHECKED = 1) Check the unusual indications of M-NET system’ remote control or centralized management system

INDICATIONS ON REMOTE CONTROL = Ed
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 5 times
FAULTS = Communication between M-NET adapters is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor unit and Outdoor unit
THE PART TO BE CHECKED = 1) The connector between indoor control board and M-NET board seperated