Saturday, November 6, 2010

Mr Slim MULTI-S CHECK CODE


MULTI-S CHECK CODE (PUMY)

ERROR CODE = 1102
POSTPONED ERROR CODE = 1202
FAULT = Discharge temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?

ERROR CODE = 1108
POSTPONED ERROR CODE = 1208
FAULT = Inner thermostat of compressor is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the S phase on outdoor board open?

ERROR CODE = 1302
POSTPONED ERROR CODE = 1402
FAULT = High-pressure is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is the ball valve opened?
2) Confirm whether indoor filter is blocked or whether outdoor short cycle occurred

ERROR CODE = 1500
POSTPONED ERROR CODE = 1600
FAULT = Refrigerant is overcharged
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?

ERROR CODE = 1501
POSTPONED ERROR CODE = 1601
FAULT = Refrigerant is insufficient
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?

ERROR CODE = 1505
POSTPONED ERROR CODE = 1605
FAULT = Vacuum operation is protected
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?

ERROR CODE = 2502
POSTPONED ERROR CODE =
FAULT = Drain pump is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether drain pipe is inclined or blocked
2) Connector of drain pipe seperated

ERROR CODE = 2503
POSTPONED ERROR CODE =
FAULT = Drain sensor (THd) is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED
1) Drain sensor is dirty
2) CN50 connector on indoor board seperated

ERROR CODE = 4115
POSTPONED ERROR CODE = 4165
FAULT = Synchronizing signal of power is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is R phase or T phase open?
2) Has fuse of R phase or T phase blown?

ERROR CODE = 4116
POSTPONED ERROR CODE =
FAULT = Rotation amount of fan is wrong (PKFY-AM)
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED
1) Is air filter blocked

ERROR CODE = 4220
POSTPONED ERROR CODE = 4320
FAULT = Voltage of inverter bus is insufficient
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is S phase open?

ERROR CODE = 4230
POSTPONED ERROR CODE = 4330
FAULT = Temperature of heat dissipation board is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is ventilation of heat dissipation board for cooling blocked

ERROR CODE = 4250
POSTPONED ERROR CODE = 4350
FAULT = IPM error (Heat current is intercepted) IPM error
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is any power phase open?
2) Has voltage of power supply failed?



ERROR CODE = 5101
POSTPONED ERROR CODE = 1202
FAULT = Thermistor (TH21) for suction temperature is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) CN20 connector on indoor board seperated

ERROR CODE = 5101
POSTPONED ERROR CODE = 1202
FAULT = Thermistor (TH1) for Discharge temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH1 connector on outdoor board seperated

ERROR CODE = 5102
POSTPONED ERROR CODE = 1211
FAULT = Thermistor (TH22) for refrigerant pipe temperature is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) CN21 connector on indoor board seperated

ERROR CODE = 5102
POSTPONED ERROR CODE = 1211
FAULT = Thermistor (TH2) for suction pressure saturation temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH2 connector on outdoor board seperated

ERROR CODE = 5103
POSTPONED ERROR CODE = 1213
FAULT = Thermistor (TH23) for gas pipe temperature is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) TH29 connector on indoor board seperated

ERROR CODE = 5105
POSTPONED ERROR CODE = 1205
FAULT = Thermistor (TH5) for condensor outlet temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH5 connector on indoor board seperated

ERROR CODE = 5106
POSTPONED ERROR CODE = 1221
FAULT = Thermistor (TH6) for outdoor temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH6 connector on indoor board seperated

ERROR CODE = 5110
POSTPONED ERROR CODE = 1214
FAULT = Thermistor (THHS) for IPM heat dissipation board temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) THHS connector on indoor board seperated

ERROR CODE = 5201
POSTPONED ERROR CODE = 1402
FAULT = Pressure sensor (63HS) is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Affirm whether gas leak or gas shortage occurred

ERROR CODE = 6600
POSTPONED ERROR CODE =
FAULT = Address double definition error
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Is the same address as the error generating origin specified?

ERROR CODE = 6602
POSTPONED ERROR CODE =
FAULT = Transmission processor H/W error
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Turn power OFF simultaneously for 2 minutes or more, Then turn them back on again.

ERROR CODE = 6603
POSTPONED ERROR CODE =
FAULT = Transmission circuit (bus) Busy error
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Wiring mistake of TB3 or TB7 on outdoor unit

ERROR CODE = 6606
POSTPONED ERROR CODE =
FAULT = Communication error with the transmission processor
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Turn power OFF simultaneously for 2 minutes or more, Then turn them back on again.

ERROR CODE = 6607
POSTPONED ERROR CODE =
FAULT = No ACK
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control = *
THE PART TO BE CHECKED = 1) Address setting is improper, or transmission cable seperated

ERROR CODE =6608
POSTPONED ERROR CODE =
FAULT = No response
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control = *
THE PART TO BE CHECKED = 1) Check the used electric wire

ERROR CODE = 6810
POSTPONED ERROR CODE =
FAULT = UR communicaton
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control = *
THE PART TO BE CHECKED = 1) Wire connection for the unit remote control transmission is poor

ERROR CODE = 7100
POSTPONED ERROR CODE =
FAULT = Over index
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Has index been exceeded

ERROR CODE = 7101
POSTPONED ERROR CODE =
FAULT = Over index
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Has an indoor unit beyond the permitted index connected

ERROR CODE = 7102
POSTPONED ERROR CODE =
FAULT = The number of connected units
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Are connected units over the number of restriction?
2) Transmission cord of indoor unit seperated

ERROR CODE = 7105
POSTPONED ERROR CODE =
FAULT = Address setting error
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Is outdoor unit address set to 000 or to a range of 51-100?

ERROR CODE = 7111
POSTPONED ERROR CODE =
FAULT = Remote control sensor is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) Is an old type remote control connected?