Do Not turn off the power supply before reading the fault codes, doing so will clear the diagnostic memory. Caution
must be taken when removing the access covers as high voltages are present.
Fault codes are displayed through the LEDs flashing at 5 times per second. Note, the green LED will flash once per second when the system is initially powered.
More specific codes may be obtained, while in the fault mode through the wireless controller
1. Press CHK to enter service mode
2. Navigate through TIMER ƒ buttons until all LEDs flash, accompanied by the internal buzzer – compare the displayed code with the table below
3. Press CLR button to clear the existing fault code (controller displays 7F)
Press ON/OFF button to exit service mode.
Initial code/display = 01
Code = 0C
Description = TA sensor open or short circuit
Initial code/display = 01
Code = 0d
Description = TC sensor open or short circuit
Initial code/display = 01
Code = 11
Description = Indoor fan motor problem
Initial code/display = 01
Code = 12
Description = Indoor PCB problem
Initial code/display = 01
Code = 04
Description = Indoor to outdoor communication (includes compressor thermostat)
Initial code/display = 01
Code = 05
Description = Indoor to outdoor communication
Initial code/display = 02
Code = 14
Description = Inverter low voltage or short circuit protection
Initial code/display = 02
Code = 16
Description = Compressor position circuit
Initial code/display = 02
Code = 17
Description = Compressor current detected during off-cycle
Initial code/display = 02
Code = 18
Description = TE or TS sensor open or short circuit
Initial code/display = 02
Code = 19
Description = Td sensor open or short circuit
Initial code/display = 02
Code = 1A
Description = Outdoor fan motor problem
Initial code/display = 02
Code = 1b
Description = TE sensor fault
Initial code/display = 02
Code = 1C
Description = Compressor drive circuit
Initial code/display = 03
Code = 07
Description = Indoor to outdoor communication (includes compressor thermostat)
Initial code/display = 03
Code = 08
Description = Indoor heat exchanger changes temperature – but in wrong direction
Initial code/display = 03
Code = 1d
Description = Compressor locked rotor current protection
Initial code/display = 03
Code = 1E
Description = Compressor - high discharge temperature
Initial code/display = 03
Code = 1F
Description = Compressor current remains too high – after current release
1 komentar:
Thanks .. I have error codes 02, 13 & 1A... does anyone know what is the #13 is for please?