must be taken when removing the access covers, as high voltages are present.
Fault diagnosis is available at three locations within the Air Conditioning system. :-
1. Remote Controller - press the check button (if installed)
2. Central Controller – press the check button (if installed)
3. Outdoor Unit – Inv & Fix switch positions 1 - 1 - 1
Code = 04
PCB = IFACE
Area = IFACE to INV
Condition = Communication failure
Criteria =
Code = 08
PCB = IN
Area = TC1 and TC2 coil sensors
Condition = Indoor heat exchange changes temperature but in wrong direction
Criteria =
Code = 0C
PCB = IN
Area = TA air temperature sensor
Condition = OC/SC
Criteria =
Code = 0b
PCB = IN
Area = Float switch circuit
Condition = OC
Criteria =
Code = 11
PCB = IN
Area = Fan motor
Condition = Short circuit
Criteria =
Code = 12
PCB = IN
Area = PCB
Condition = EEPROM failure
Criteria =
Code = 14
PCB = INV
Area = DC current sensor
Condition = INV compressor or transistor SC. Sensor OC
Criteria =
Code = 17
PCB = INV
Area = DC current sensor
Condition = INV compressor current detected during off cycle.
Criteria =
Code = 18
PCB = IFACE
Area = TE1 defrost sensor
Condition = OC/SC
Criteria =
Code = 1C
PCB = IFACE
Area = PCB
Condition = EEPROM failure
Criteria =
Code = 1d
PCB = INV
Area = DC current sensor
Condition = INV compressor overload
Criteria = > 1.5 times full load current
Code = 1F
PCB = INV
Area = DC current sensor
Condition = Excessive current detected after current release
Criteria =
Code = 21
PCB = INV
Area = INV Compressor
Condition = HP switch or klixon
Criteria = > 363 psig – 25 Bar
Code = 22
PCB = IFACE
Area = Pd sensor
Condition = Excessive pressure
Criteria = > 406 psig – 28 Bar
Code = 87
PCB = IFACE
Area = Input Phase
Condition = Missing phase
Criteria =
Code = 89
PCB = IFACE
Area = IN capacity settings
Condition = Too high
Criteria = > 135% outdoor unit
Code = 8d
PCB = IFACE
Area = Outdoor units - number of
Condition = Has fallen since last set up
Criteria =
Code = 8E
PCB = IFACE
Area = Outdoor units - number of
Condition = Is too high
Criteria = > 5
Code = 8F
PCB = FIX unit address
Area = Duplicated
Condition = When manually set
Criteria =
Code = 93
PCB = IN
Area = TC1 gas sensor
Condition = OC/SC
Criteria =
Code = 94
PCB = IN
Area = TC2 liquid sensor
Condition = OC/SC
Criteria =
Code = 95
PCB = IFACE
Area = PQ
Condition = Communication failure
Criteria = No INV outdoor unit
Code = 96
PCB = IFACE
Area = IN units - number of
Condition = Too many
Criteria = > 40
Code = 97
PCB = Central
Area = XY
Condition = Communication failure
Criteria =
Code = 98
PCB = Central
Area = XY
Condition = Duplicated addresses
Criteria =
Code = 99
PCB = Remote
Area = ABC
Condition = Communication failure
Criteria =
Code = 9A
PCB = IN
Area = TC1 gas sensor
Condition = Unauthorized temperature change
Criteria = Changed by > 5ºC after 15 minutes operation
Code = 9F
PCB = IN
Area = TC1 gas sensor and TC2 liquid sensor
Condition = Insufficient performance
Criteria = Changed by < 5ºC after 60 minutes operation
Code = A0
PCB = IFACE
Area = TD1 discharge sensor
Condition = OC/SC
Criteria =
Code = A1
PCB = IFACE
Area = TD2 discharge sensor
Condition = OC/SC
Criteria =
Code = A2
PCB = IFACE
Area = TS1 suction sensor
Condition = OC/SC
Criteria =
Code = A6
PCB = IFACE
Area = TD1 discharge sensor
Condition = High discharge temperature
Criteria = > 130ºC 3 times
Code = A7
PCB = IFACE
Area = TS1 suction sensor
Condition = High suction temperature
Criteria = > 60ºC for 10 minutes, 3 times
Code = AA
PCB = IFACE
Area = Pd pressure sensor
Condition = OC
Criteria =
Code = Ab
PCB = IFACE
Area = Pd and Ps pressure sensors
Condition = OC or crossed
Criteria =
Code = AE
PCB = IFACE
Area = TD1 discharge sensor
Condition = High discharge temperature (low load condition)
Criteria = > 110ºC, 3 times
Code = AF
PCB = IFACE
Area = Phase rotation
Condition = Incorrect
Criteria =
Code = b4
PCB = IFACE
Area = Ps sensor
Condition = Suction pressure too high during operation
Criteria = OC or < 138 psig – 9.5 Bar
Code = b5
PCB = IN
Area = CN17
Condition = Indoor unit emergency circuit
Criteria = Resistive connection
Code = b6
PCB = IN
Area = CN17
Condition = Indoor unit emergency circuit
Criteria = SC
Code = b7
PCB = Central
Area = Fault in connected group
Condition = Check local controller
Criteria =
Code = b9
PCB = IN
Area = Pressure sensor
Condition = OC
Criteria =
Code = bb
PCB = IFACE
Area = TD2 discharge sensor
Condition = High discharge temperature
Criteria = > 130ºC 3 times
Code = bd
PCB = IFACE
Area = TD2, Ps, Pd
Condition = FIX compressor contactor fault
Criteria = Operation detected during off cycle
Code = bE
PCB = IFACE
Area = Ps sensor
Condition = Low pressure
Criteria = < 3 psig – 0.21 Bar
Code = cF
PCB = IN
Area = Main and relay PCBs
Condition = Communication failure
Criteria =
Code = d1
PCB = IFACE
Area = INV outdoor unit
Condition = Duplicated within a system
Criteria =
Code = d2
PCB = IFACE
Area = FIX unit fault
Condition = Press SW04 for several seconds
Criteria = Fan of outdoor unit runs
Code =d3
PCB = IFACE
Area = TH inverter overheat sensor
Condition = OC/SC
Criteria =
Code = d4
PCB = IFACE
Area = TK1 oil level sensor primary side
Condition = OC/SC
Criteria =
Code = d5
PCB = IFACE
Area = TK2 oil level sensor secondary side
Condition = OC/SC
Criteria =
Code = d6
PCB = IFACE
Area = TK3 oil level sensor
Condition = OC/SC
Criteria =
Code = d7
PCB = IFACE
Area = TK1, 2, 3
Condition = Oil level low
Criteria = > 2 hours
Code = d8
PCB = IFACE
Area = TK1 oil level sensor primary side
Condition = No oil flow detected
Criteria = No temp change during oil level management
Code = d9
PCB = IFACE
Area = TK2 oil level sensor secondary side
Condition = No oil flow detected
Criteria = No temp change during oil level management
Code = dA
PCB = INV
Area = IGBT overheating
Condition =
Criteria =
Code = db
PCB = IFACE
Area = TK1 and TK2
Condition = No oil flow detected
Criteria = No temp change during oil level management
Code = dC
PCB = IFACE
Area = TK1
Condition = High oil temperature
Criteria = > 50ºC
Code = dd
PCB = IFACE
Area = FIX outdoor unit
Condition = Operation detected during off cycle
Criteria =
Code = dE
PCB = IFACE
Area = IN unit
Condition = Automatic addressing failure
Criteria =
Code = dF
PCB = IFACE
Area = Outdoor unit
Condition = Automatic addressing failure
Criteria =
Code = E1
PCB = IFACE
Area = FIX compressor 1
Condition = HP switch, klixon or overload relay
Criteria = Pd is > 363 psig – 25 Bar
Code = E5
PCB = IFACE
Area = INV compressor
Condition = HP switch or klixon
Criteria = Pd is > 363 psig – 25 Bar
Code = E6
PCB = IFACE
Area = FIX compressor 1
Condition = HP switch, klixon or overload relay
Criteria = Pd is > 363 psig – 25 Bar
Code = Eb
PCB = IFACE
Area = b6 code received from IN unit
Condition =
Criteria =
Code = F0
PCB = IFACE
Area = FIX compressor 2
Condition = HP switch, klixon or overload relay
Criteria = Pd is > 363 psig– 25 Bar
Code = F1
PCB = IFACE
Area = FIX compressor 2
Condition = HP switch, klixon or overload relay
Criteria = Pd is > 363 psig– 25 Bar