Sunday, November 21, 2010

VRF Trouble Shooting – Fujitsu

1 komentar
VRF Trouble Shooting – Fujitsu

Pipework
• Always check that the pipework follows the limitations in the corresponding user guides
• Use of dry nitrogen while brazing or when pipework open to atmosphere is vitale
• Always use a good electronic Torr gauge such as 617981 while evacuating
• If multiple indoor units are low on capacity, system is probably undercharged
• If one indoor unit is low on capacity, strainer is probably blocked
Outdoor Unit
• Gas pressures are frequently a bad guide to system gas charge
• Check the condensor coil is not blocked and airflow not impeded
• Make sure system is not over indexed if all indoor units are in the same area (inverter models)
Indoor Units & Heat Recovery (HR & RB) Boxes
• These items have pipework strainers which can, and do, block. Check these first.
• Temperature difference between return and supply air of 10C cooling/15C heating indicates system ok
• Always check condition of return air filters and clean if necessary
Controllers and Wiring
• All VRF systems have self diagnostics at the controller - see below
• Ensure control wiring is run in screened cable without exception (1mm 2 core CY suggested)
• Ensure screened cable is Earthed at one end only

Fault Diagnostic Codes
Fujitsu J Series and Airstage follow the fault codes below -
Indoor Fault Codes - access from handset • LED Codes refer to flash type

Handset = E:00
Red LED =
Green LED =
Yellow LED = No Fault Currently
Meaning =
Remedy = Run system again

Handset = E:02
Red LED = Rapid
Green LED = Rapid
Yellow LED = Model Abnormal
Meaning =
Remedy = Check DIP switches

Handset = E:03
Red LED = 5 times
Green LED = Rapid
Yellow LED = 2 times
Meaning = Processor Failure
Remedy = PCB failure

Handset = E:04
Red LED = Rapid
Green LED = Rapid
Yellow LED = Rapid
Meaning = Power Abnormal
Remedy = Swap 2 phases

Handset = E:06
Red LED = Rapid
Green LED = 4 times
Yellow LED = 1 TIme
Meaning = EEPROM Error
Remedy = PCB Failure

Handset = E:07
Red LED = Rapid
Green LED = 4 time
Yellow LED = 2 Times
Meaning = EEPROM Error
Remedy = PCB Failure

Handset = E:09
Red LED = 2 times
Green LED =
Yellow LED =
Meaning = Room Sensor Failure
Remedy = Check/Replace

Handset = E:0A
Red LED = 3 times
Green LED = Rapid
Yellow LED = 1 Time
Meaning = Middle Pipe Sensor Fail
Remedy = Check/Replace

Handset = E:0b
Red LED = 3 times
Green LED = Rapid
Yellow LED = 2 Times
Meaning = Inlet Pipe Sensor Fail
Remedy = Check/Replace

Handset = E:0C
Red LED = 3 times
Green LED = Rapid
Yellow LED = 3 Times
Meaning = Outlet Pipe Sensor Fail
Remedy = Check/Replace

Handset = E:0d
Red LED = 7 times
Green LED = Rapid
Yellow LED =
Meaning = Fan Temp Sensor Fail
Remedy = Check/Replace

Handset = E:11
Red LED = 4 times
Green LED = Rapid
Yellow LED =
Meaning = Drainage Failure
Remedy = Drains/Float Sw/Pump

Handset = E:12
Red LED = Rapid
Green LED = 7 times
Yellow LED =
Meaning = Room Temp too high/low
Remedy = Is unit over/Undersized

Handset = E:13
Red LED = 6 times
Green LED = Rapid
Yellow LED =
Meaning = Fan Failure
Remedy = Check filters/motor

Handset = E:18
Red LED = 5 times
Green LED = Rapid
Yellow LED = 1 or 4 Times
Meaning = Control Comms Failure
Remedy = Check Controller Wiring

Handset = E:1F
Red LED = Rapid
Green LED = 5 times
Yellow LED = 1 TIme
Meaning = Transmission Failure
Remedy = Check Control Wiring

Handset = E:20
Red LED = Rapid
Green LED = 5 times
Yellow LED = 2 Times
Meaning = Node Error
Remedy = Check Control Wiring

Handset = E:21
Red LED = Rapid
Green LED = 6 times
Yellow LED =
Meaning = Parralel Comms Error
Remedy = Check Control Wiring

Handset = E:32
Red LED = Rapid
Green LED = 7 times
Yellow LED =
Meaning = Outdoor Unit Error
Remedy = Check Outdoor Unit

Outdoor Codes - On Outdoor PCB • When LED1 flashes rapidly the other LEDS below -

LED = 1 flash
1 = Rapid
2 = Comp1 Fail
3 = Dis Sens1
4 = Dis Press
5 = Phase Fail
6 = ID Unit Fail

LED = 2 flashes
1 = Rapid
2 = Comp2 Fail
3 = Dis Sens2
4 = Liq Press
5 = Power Freq
6 = ID1 Fail

LED = 3 flashes
1 = Rapid
2 = Comp3 Fail
3 = Dis Sens3
4 =
5 = PCB Fail
6 = ID1 Fail

LED = 4 flashes
1 = Rapid
2 = Dis Temp1
3 = In Pipe1
4 = Comp Seize
5 = PCB Fail
6 = ID1 Fail

LED = 5 flashes
1 = Rapid
2 = Dis Temp2
3 = In Pipe2
4 = Hi Current
5 =
6 = ID1 Fail

LED = 6 flashes
1 = Rapid
2 = Dis Temp3
3 = In Pipe3
4 = CT Error
5 = PCB Fail
6 = ID1 Fail

LED = 7 flashes
1 = Rapid
2 = HP Trip
3 = Out Pipe1
4 = Oil Low
5 = PCB Fail
6 = ID1 Fail

LED = 8 flashes
1 = Rapid
2 = LP Trip
3 = Out Pipe2
4 =
5 = Comms Fail
6 = ID1 Fail

LED = 9 flashes
1 = Rapid
2 = Pump
3 = Out Pipe3
4 = L startup
5 = Comms Fail
6 =

LED = 10 flashes
1 = Rapid
2 = Down
3 = Suct Pipe
4 =
5 =
6 = ID1 Fail

LED = 11 flashes
1 = Rapid
2 = Error
3 = Air Sensor
4 =
5 =
6 =

If all PCB’s flash rapidly check DIP switch settings
Read More ->>

Panasonic Fault codes - FS Series

0 komentar
Fault Codes – FS Series
Current Models R410a
Pressing Check on the wired remote while CHECK is flashing will give the Fault and the address of the unit with the Fault
Pressing Timer Set with the fault displayed will display a second code giving further information (detail code)
Pressing Check for 5 seconds will check past faults
On wireless handsets press the temp up for 5 seconds to enter error check mod
Scroll through the codes using the temp up button until a beep is heard from the indoor unit
Press set and repeat until the full code is displayed

F Code Display  = F15
Detail Display  = 01
Outdoor LED
302  =
303  = Flash
304  = Flash
305  = Flash
306  = Flash
307  = See Note 1
308  = See Note 1
309  =
Measurig Fault Code = Drain Failure

F Code Display  = F16
Detail Display  = 01
Outdoor LED
302  =
303  =
304  =
305  =
306  =
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = Louvre Failure

F Code Display  = F17
Detail Display  = 01
Outdoor LED
302  = 
303  =
304  =
305  =
306  =
307  =
308  = See Note 1
309  = See Note 1
Measurig Fault Code = Option Problem

F Code Display  = F17
Detail Display  = 02
Outdoor LED
302  = Flash
303  = Flash
304  =
305  =
306  =
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = DC Fan Motor Failure

F Code Display  = F20
Detail Display  = 01
Outdoor LED
302  =
303  =
304  =
305  = Flash
306  =
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = ID Air Sensor

F Code Display  = F20
Detail Display  = 02
Outdoor LED
302  = Flash
303  =
304  =
305  = Flash
306  =
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = RC Air Sensor

F Code Display  = F21
Detail Display  = 01
Outdoor LED
302  =
303  = Flash
304  =
305  = Flash
306  =
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = ID Pipe Sensor

F Code Display  = F25
Detail Display  = 01
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *Only for Older Models with LEDS 1-6
308  = See Note 1
309  = See Note 1
Measurig Fault Code = Addressing Incorrect

F Code Display  = F26
Detail Display  = 01
Outdoor LED
302  =
303  =
304  = Flash
305  =
306  = Flash
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = RC Comms Problem

F Code Display  = F27
Detail Display  = 01
Outdoor LED
302  =
303  = Flash
304  = Flash
305  =
306  = Flash
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = ID - OD Comms Disconnected ID

F Code Display  = F27
Detail Display  = 02
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *Only for Older Models with LEDS 1-6
308  = See Note 1
309  = See Note 1
Measurig Fault Code = ID - OD Comms Connection ID

F Code Display  = F27
Detail Display  = 05
Outdoor LED
302  = Flash
303  = Flash
304  = Flash
305  =
306  = Flash
307  = Flash
308  = See Note 1
309  = See Note 1
Measurig Fault Code = ID - OD Comms Connection ID

F Code Display  = F27
Detail Display  = 01
Outdoor LED
302  = Flash
303  =
304  = Flash
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = ID - OD Comms Disconnected OD

F Code Display  = F27
Detail Display  = 02
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code = ID - OD Comms Connection OD

F Code Display  = F27
Detail Display  = 05
Outdoor LED
302  =
303  =
304  =
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = ID - OD Comms Connection OD

F Code Display  = F29
Detail Display  = 01
Outdoor LED 
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code = ID PCB Setting

F Code Display  = F30
Detail Display  = 01
Outdoor LED
302  =
303  =
304  =
305  =
306  =
307  = Flash
308  =
309  =
Measurig Fault Code = ID/OD Capacity Incorrect

F Code Display  = F30
Detail Display  = 02
Outdoor LED
302  =
303  =
304  = Flash
305  =
306  =
307  = Flash
308  =
309  =
Measurig Fault Code = Phase Rotation

F Code Display  = F31
Detail Display  = 01
Outdoor LED
302  =
303  = Flash
304  =
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = Low Pressure

F Code Display  = F31
Detail Display  = 02
Outdoor LED
302  = Flash
303  =
304  =
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = High Pressure

F Code Display  = F31
Detail Display  = 06
Outdoor LED
302  =
303  =
304  = Flash
305  = Flash
306  = 
307  =
308  =
309  =
Measurig Fault Code = Reversing Valve

F Code Display  = F31
Detail Display  = 08
Outdoor LED
302  =
303  = Flash
304  =
305  =
306  =
307  = Flash
308  =
309  =
Measurig Fault Code = Indoor Coil Iced

F Code Display  = F31
Detail Display  = 09
Outdoor LED
302  =
303  = Flash
304  = Flash
305  = Flash
306  =
307  =
308  =
309  =
Measurig Fault Code = Gas Leak

F Code Display  = F31
Detail Display  = 10
Outdoor LED
302  =
303  = Flash
304  = Flash
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = Low Gas, Valve Shut or Blockage

F Code Display  = F32
Detail Display  = 03
Outdoor LED
302  =
303  =
304  = Flash
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = Inverter Low dc Volts

F Code Display  = F32
Detail Display  = 04
Outdoor LED
302  = Flash
303  = Flash
304  =
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = Inverter IPM

F Code Display  = F32
Detail Display  = 05
Outdoor LED
302  = Flash
303  = Flash
304  = 
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = Compressor Overcurrent

F Code Display  = F32
Detail Display  = 06
Outdoor LED
302  = Flash
303  = Flash
304  =
305  = Flash
306  =
307  =
308  =
309  =
Measurig Fault Code = Compressor Disch Temp High

F Code Display  = F32
Detail Display  = 08
Outdoor LED
302  = Flash
303  = 
304  = Flash
305  = Flash
306  =
307  =
308  =
309  =Inverter PFC
Measurig Fault Code = 

F Code Display  = F32
Detail Display  = 09
Outdoor LED
302  = Flash
303  =
304  =
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = Inverter High dc Volts

F Code Display  = F32
Detail Display  = 10
Outdoor LED
302  = Flash
303  = Flash
304  = Flash
305  = 
306  =
307  =
308  =
309  =
Measurig Fault Code = Compressor Rotation Problem

F Code Display  = F33
Detail Display  = 01
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code = Compressor High Current

F Code Display  = F33
Detail Display  = 02
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code = High Discharge Temp

F Code Display  = F35
Detail Display  = 2
Outdoor LED
302  =
303  = Flash
304  =
305  =
306  = Flash
307  =
308  =
309  =
Measurig Fault Code = OD dc Fan Motor Locked

F Code Display  = F40
Detail Display  = 01
Outdoor LED
302  =
303  =
304  = Flash
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = OD Outlet Sensor

F Code Display  = F40
Detail Display  = 11
Outdoor LED
302  =
303  =
304  =
305  = Flash
306  =
307  =
308  =
309  =
Measurig Fault Code = Suction Temp

F Code Display  = F40
Detail Display  = 21
Outdoor LED
302  = Flash
303  =
304  = Flash
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = OD Liquid Sensor

F Code Display  = F40
Detail Display  = 31
Outdoor LED
302  = Flash
303  = Flash
304  = Flash
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = Defrost Sensor

F Code Display  = F40
Detail Display  = 51
Outdoor LED
302  =
303  = Flash
304  = Flash
305  =
306  =
307  =
308  =
309  =
Measurig Fault Code = Discharge Sensor

F Code Display  = F40 
Detail Display  = 41
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code = Discharge Sensor

F Code Display  = F40 
Detail Display  = 61
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code =  OD Pipe Sensor

F Code Display  = F41
Detail Display  = 02
Outdoor LED
302  = Flash
303  = Flash
304  =
305  =
306  =
307  = Flash
308  =
309  =
Measurig Fault Code = HP Switch

F Code Display  = F41
Detail Display  = 03
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code =  Heating HP Switch

F Code Display  = F41
Detail Display  = 11
Outdoor LED
302  = Flash
303  =
304  =
305  =
306  =
307  = Flash
308  =
309  =
Measurig Fault Code = Low Pressure Sensor

F Code Display  = F42
Detail Display  = 01
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code =  Compressor Current Sensor

F Code Display  = F42
Detail Display  = 11
Outdoor LED
302  =
303  = Flash
304  =
305  = Flash
306  =
307  =
308  =
309  =
Measurig Fault Code = Current Sensor Open

F Code Display  = F44
Detail Display  = 01
Outdoor LED
302  = Flash
303  =
304  =
305  = Flash
306  =
307  =
308  =
309  =
Measurig Fault Code = Inverter IPM Sensor

F Code Display  = F49
Detail Display  = 01
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code =  OD PCB Setting Faulty

F Code Display  = F49
Detail Display  = 02
Outdoor LED
302  = *
303  = *
304  = *
305  = *
306  = *
307  = *
308  = *
309  = *Only for Older Models with LEDS 1-6
Measurig Fault Code =  OD PCB Setting Faulty

Note 1: LED308 is lit if the master unit is the problem or 309 for the slave
LED 301 is lit when power is supplied to the PCB


A General Guide To Urban Style Products

Pipework
• Pipe sizes and lengths should be as the relevant Technical Guide
• Both lines should be insulated
• No line accessories or oil traps should be fitted
• In cooling mode the suction line should sweat, but not freeze
• In heating mode both pipes should be between 30 and 60C
• Pipework should be refrigeration quality
• Look for restrictions. They could cause compressor failures.
Outdoor Unit
• Discharge Temperature should be between 50 and 70C
• Suction Temperature should be between -3 and 4C
• Check Suction Line is sweating in cooling - problem if not!
• Hot Recip. Compressor = PROBLEM
• Sweating/Frost on expansion line - undercharged
Indoor Unit
• Is it level? Have we adequate drainage?
• Smells are always due to site conditions or drains.
• Flashing lights? = Fault Diagnostics - see over
• When were the filters last cleaned?
• Is the unit too large/small (between 5/20 air circs/hr)
• Is the air short cycling?
Controller
• Is it a wired or wireless handset.
• Is the handset too far away?
• When were the batteries changed last?
• With wired handset, check for interference.
• Is the unit in Emergency Mode?
• Check unit and controller channels compatible
Wiring
• Interconnecting comms wiring is low voltage
• If you have 230V live, check you have a neutral as well
• Check Mains and comms cable not swapped round
• Multi linked systems must be set up as such
• Check voltage drops! Check it isn’t down to Earth!
• Interconnecting cables should be circular crimped


Selecting Emergency Mode is done at the Indoor and Outdoor Unit PCB.
It bypasses the Control Sensors and should not be done for more than 30 minutes.

Indoor PCB - Swicth SS1 to Emergency Setting
Outdoor PCB - Swicth Emergency Swicth 1 to ON
Outdoor PCB - Swicth Emergency Swicth 2 to Cool or

Wire E - 1 - 2 - 3
All Earth - Live - Neutral - Comms

Sensor Resistances – Use to check Thermistor
Air and Pipe sensors apply to indoor AND outdoor units
The discharge sensor is only in the outdoor unit.
If the fault code suggests the sensor is a problem but you
get a sensor reading as to the right then either the connection or PCB is at fault.

Sensor - At 10C - At 20C - At 30C
Air Sensor - 40K 0hms - 25K 0hms - 16K 0hms
Pipe Sensor - 40K 0hms - 25K 0hms - 16K 0hms
Discharge Sensor - 480K 0hms - 293K 0hms - 184K 0hms


Fault codes on Panasonic US systems can be checked using both the wired remote controller and the indoor and outdoor unit LEDs. In case of a malfunction
the wired controller will give a fault code as shown below in conjunction with the accompanying LED codes.
The wireless controller can be used to interrogate a fault, if required, as described below.
1 - Press Inspection/Test button on wireless handset. 0 flashes in Unit Number display on handset.
2 - Press Up/Down button until unit starts to bleep.
3 - 1 continuous beep means No fault. 3 short beeps - follow all steps below. 1 short beep - follow step 4 until you get a continuous beep.
4 - Press the handset MODE button. Press the up/down arrow button until you get 2 short bleeps, or one continuous bleep.
5 - Press the MODE button again. Press the up/down arrow button until you get one continuous bleep.
6 - The fault code is now displayed!

RC Display  = Normal
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Normal Operation
Caused By = Normal Running

RC Display  = A1
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Various
H2P/HBP  = Various
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Indoor PCB Failure
Caused By = PCB Failure or External Spike

RC Display  = A3
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = High Water Level
Caused By = Float Switch Tripped - Check your drains

RC Display  = A6
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Fan Motor Failure - ID Unit
Caused By = Fan Motor not running fast enough

RC Display  = A7
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Louvre Motor Failure
Caused By = Louvre Motor Microswitch

RC Display  = AF
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Drain System Failure
Caused By = Float Switch Trip while compressor

RC Display  = AJ
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Faulty Capacity Setting
Caused By = Ring Technical Support

RC Display  = C4
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Pipe Sensor Failure
Caused By = Thermistor reading incorrect

RC Display  = C9
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Air Sensor Failure
Caused By = Thermistor reading incorrect

RC Display  = CJ
Indoor Unit LEDs
Panel   = Flash
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Handset Thermistor failure
Caused By = Thermistor reading incorrect

RC Display  = E0
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = Off
Fault Means = Safety Device Trip
Caused By = High Compressor or Fan Temperature

RC Display  = Various
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = On
H1P  = Various
H2P  = Various
Fault Means = Outdoor PCB Failure
Caused By = PCB Failure or External Spike

RC Display  = Various
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = 
H2P/HBP  = 
Outdoor Unit LEDs
HAP  = Off
H1P  = Off
H2P  = Off
Fault Means = Outdoor Power Supply or PCB Failure
Caused By = Check your power supply including neutral

RC Display  = E3
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = Off
Fault Means = HP Trip
Caused By = Excess Refrigerant, blockage or contamination

RC Display  = E4
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = Off
Fault Means = LP Trip
Caused By = Refrigerant shortage, blockage or contamination

RC Display  = E9
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Expansion Valve Failure
Caused By = Expansion valve closed or open circuit

RC Display  = F3
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = Off
Fault Means = Discharge Temperature Error
Caused By = Refrigerant shortage or blockage

RC Display  = H3
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = On
Fault Means = Failed HP Switch
Caused By = HP trip when compressor off

RC Display  = H9
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = On
Fault Means = Failed OD Temperature Sensor
Caused By = Thermistor reading incorrect

RC Display  = J3
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = On
Fault Means = Failed Discharge Sensor
Caused By = Thermistor reading incorrect

RC Display  = J6
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = On
H2P  = On
Fault Means = Failed OD Pipe Sensor
Caused By = Thermistor reading incorrect

RC Display  = U0
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Various
H1P  = Various
H2P  = Various
Fault Means = Gas shortage
Caused By = Refrigerant shortage or blockage

RC Display  = U1
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Flash
H1P  = Off
H2P  = On
Fault Means = Phase protection
Caused By = Swap two phases to operate correctly

RC Display  = U4
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Various
H1P  = Various
H2P  = Various
Fault Means = ID to OD Unit Transmission failure
Caused By = Faulty connection or PCB

RC Display  = UF
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Various
H1P  = Various
H2P  = Various
Fault Means = ID to OD Unit Transmission failure
Caused By = Faulty connection or PCB

RC Display  = U5
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Various
H1P  = Various
H2P  = Various
Fault Means = ID Unit to RC Transmission failure
Caused By = Faulty connection or PCB

RC Display  = U8
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Various
H1P  = Various
H2P  = Various
Fault Means = RC to RC Transmission failure
Caused By = Faulty connection or RC

RC Display  = UA
Indoor Unit LEDs
Panel   = Off
H1P/HAP  = Flash
H2P/HBP  = Flash
Outdoor Unit LEDs
HAP  = Various
H1P  = Various
H2P  = Various
Fault Means = Field SettingSwitch
Caused By = Ring Technical Support Failure

Read More ->>

Saturday, November 20, 2010

Panasonic Fault Diagnostics – Older Style FS Units R22

1 komentar
Fault Diagnostics – Older Style FS Units R22
First generation series 11NP Series with E style fault codes
Press check on the Wired Controller to call up the Fault Codes.

Fault Code At Remote  = E1
Indoor Unit PCB
LED1   = Flash
LED2   = Flash
LED3   = Flash
Measuring Of Fault Code = Signal from RC to ID Unit faulty

Fault Code At Remote  = E2
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
Measuring Of Fault Code = Float Switch

Fault Code At Remote  = E3
Indoor Unit PCB
LED1   =
LED2   = Lit
LED3   = 
Measuring Of Fault Code = Air Sensor Faulty

Fault Code At Remote  = E4
Indoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
Measuring Of Fault Code = Pipe sensor Faulty

Second Generation 21NP Series with F Fault Codes
Press Check on the Wired Controller to call up the Fault Codes

Fault Code At Remote  = F2
Indoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   =
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Float switch

Fault Code At Remote  = F3
Indoor Unit PCB
LED1   =
LED2   = Lit
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Indoor Air Sensor Faulty

Fault Code At Remote  = F4
Indoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Indoor Air Sensor Faulty

Fault Code At Remote  = F5
Indoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   = Lit
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Signal from RC to ID faulty

Fault Code At Remote  = F5
Indoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = No Signal from ID to RC

Fault Code At Remote  = F6
Indoor Unit PCB
LED1   =
LED2   = Lit
LED3   = Lit
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = Signal from ID to OD faulty

Fault Code At Remote  = F6
Indoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
LED4   = Lit
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Measuring Of Fault Code = No Signal from Od to ID

Fault Code At Remote  = F13
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   = Lit
Measuring Of Fault Code = OD Unit Overcurrent Protection

Fault Code At Remote  = F15
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   =
LED4   =
Outdoor Unit PCB
LED1   = Lit
LED2   = Lit
LED3   =
LED4   =
Measuring Of Fault Code = HP Switch

Fault Code At Remote  = F18
Indoor Unit PCB
LED1   = Lit
LED2   =
LED3   = Lit
LED4   =
Outdoor Unit PCB
LED1   =
LED2   =
LED3   = Lit
LED4   =
Measuring Of Fault Code = Outdoor Pipe Sensor Faulty

Read More ->>
 