Monday, January 2, 2012

Error Monitor Lamps SANYO Multi System Air Conditioner CLM 1972/2472/3172

0 komentar
Trouble Diagnosis by Error Monitor Lamps Remove the top plate of outdoor unit and the cover of Electrical Component Box. The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box. (Fig.1) Display of the Error Monitor Lamps If a protective device has activated or there is a sensor failure in the outdoor unit, the 4 error monitor lamps on the outdoor control circuit board will indicate the nature of the trouble. Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = OFF 
ERR 2 = OFF 
ERR 3 = ON 
Error Contents = Sensor for compressor discharge temp 

Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = ON 
ERR 2 = OFF 
ERR 3 = ON Error Contents = Sensor for heat excharge temp 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = OFF 
ERR 2 = OFF 
ERR 3 = OFF 
Error Contents = Sensor for branch pipe A (Narrow tube) 

Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = ON 
ERR 2 = OFF 
ERR 3 = OFF 
Error Contents = Sensor for branch pipe B (Narrow tube) 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = ON 
ERR 2 = OFF 
ERR 3 = OFF 
Error Contents = Sensor for branch pipe C (Narrow tube) 

Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = OFF 
ERR 2 = ON 
ERR 3 = OFF 
Error Contents = Sensor for branch pipe D (Narrow tube) 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = ON 
ERR 2 = OFF 
ERR 3 = ON 
Error Contents = Outdoor temp sensor 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = OFF 
ERR 2 = ON 
ERR 3 = OFF 
Error Contents = Sensor for branch pipe A (Wide tube) 

 Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = ON 
ERR 2 = ON 
ERR 3 = OFF 
Error Contents = Sensor for branch pipe B (Wide tube) 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = ON 
ERR 2 = ON ERR3 = OFF 
Error Contents = Sensor for branch pipe C (Wide tube) 

Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = OFF 
ERR 2 = OFF 
ERR 3 = ON 
Error Contents = Sensor for branch pipe D (Wide tube) 

Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = OFF 
ERR 2 = ON 
ERR 3 = ON 
Error Contents = HIC circuit trouble (current, temp) 

Error Monitor Lamp 
ERR 0 = OFF 
ERR 1 = ON 
ERR 2 = ON 
ERR 3 = ON 
Error Contents = Actuation of comp over load relay 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = OFF 
ERR 2 = ON 
ERR 3 = ON Error Contents = Actuation of freeze protection function 

Error Monitor Lamp 
ERR 0 = ON 
ERR 1 = ON 
ERR 2 = ON 
ERR 3 = ON 
Error Contents = Outdoor unit error. Detail of error message indicate on indoor LED
Read More ->>

Friday, December 30, 2011

SANYO SAP-KRV9AEH+SAP-CRV9AEH & SAP-KRV12AEH+SAP-CRV12AEH ERROR CODE

1 komentar
Troubleshooting from Error Display NOTE 4 minutes after protection stop of compressor, the malfunction is shown in error code. In other situation, the malfunction will be displayed by press the light button for 6 times within 4 seconds. 

Code = 1 
Malfunction = Storage slug 
Error Display Dual 8 Display = EE 
LED = Heating LED-pause 3 seconds and blink 15 times 
Repair Method = Replace indoor main board. 

Code = 2 
Malfunction = Indoor PCB malfunction 
Error Display Dual 8 Display = EE 
LED = Heating LED-pause 3 seconds and blink 15 times 
Repair Method = Replace indoor main board. 

Code = 3 
Malfunction = Anti-freezing protection 
Error Display Dual 8 Display = E2 
LED = Running LED-pause 3 seconds and blink 2 times 
Repair Method = Outdoor ambient temperature is too low. 

Code = 4 
Malfunction = Overload of system 
Error Display Dual 8 Display = H4 
LED = Heating LED-pause 3 seconds and blink 4 times 
Repair Method = System is abnormal, check if the evaporator and condenser is dirty and blocked. 

Code = 5 
Malfunction = No motor of indoor unit feedback Indoor pipe 
Error Display Dual 8 Display = H6 
LED = Running LED-pause 3 seconds and blink 11 times 
Repair Method = Is electromotor mounted normally ? 

Code = 6 
Malfunction = temperature sensor malfunction Internal ambient 
Error Display Dual 8 Display = F2 
LED = Cooling LED-pause 3 seconds and blink 2 times 
Repair Method = Is it loose ? Measure the resistance value with universal meter 

Code = 7 
Malfunction = temperature sensor malfunction 
Error Display Dual 8 Display = F1 
LED = Cooling LED-pause 3 seconds and blink 1 time 
Repair Method = Is it loose ? Measure the resistance value with universal meter 

Code = 8 
Malfunction = Zero passage abnormal 
Error Display Dual 8 Display = UF 
LED = Heating and cooling LED blink 7 times at the same time 
Repair Method = Replace indoor main board. 

Code = 9 
Malfunction = Overload of compressor 
Error Display Dual 8 Display = H3 
LED = Heating LED-pause 3 seconds and blink 3 times 
Repair Method = Inspect connection state of the overload wire. 

Code = 10 
Malfunction = Startup failure 
Error Display Dual 8 Display = LC 
LED = Heating LED-pause 3 seconds and blink 11 times 
Repair Method = Check if the resistance of compressor and resistance to ground is normal. If the compressor is normal, the outdoor main board may be wrong. 

Code = 11 
Malfunction = No motor of outdoor unit feedback 
Error Display Dual 8 Display = UH 
LED = Heating and cooling LED blink 8 times at the same time 
Repair Method = This malfunction may happen when outdoor DC electromotor is used. 

Code = 12 
Malfunction = Over current protection 
Error Display Dual 8 Display = E5 
LED = Running LED-pause 3 seconds and blink 5 times 
Repair Method = Is electric network variable ? 

Code = 13 
Malfunction = 4-way valve conversion abnormal 
Error Display Dual 8 Display = U7 
LED = Cooling LED-pause 3 seconds and blink 20 times 
Repair Method = Replace 4-way valve. 

Code = 14 
Malfunction = Phase current detection malfunction of compressor 
Error Display Dual 8 Display = U1 
LED = Heating LED-pause 3 seconds and blink 13 times 
Repair Method = Replace outdoor main board. 

Code = 15 
Malfunction = Sync failure 
Error Display Dual 8 Display = H7 
LED = Heating LED-pause 3 seconds and blink 7 times 
Repair Method = Check if the resistance of compressor and resistance to ground is normal. If the compressor is normal, the outdoor main board may be wrong. 

Code = 16 
Malfunction = Current detection malfunction of complete unit Outdoor ambient 
Error Display Dual 8 Display = U5 
LED = Cooling LED-pause 3 seconds and blink 13 times 
Repair Method = Replace outdoor main board. 

Code = 17 
Malfunction = temperature sensor malfunction 
Error Display Dual 8 Display = F3 
LED = Cooling LED-pause 3 seconds and blink 3 times 
Repair Method = Is it loose ? Measure the resistance value with universal meter 

Code = 18 
Malfunction = Discharge protection of compressor 
Error Display Dual 8 Display = F4 
LED = Running LED-pause 3 seconds and blink 4 times  
Repair Method = Is it loose ? Measure the resistance value with universal meter 

Code = 19 
Malfunction = Break-circuit and short-circuit of outdoor discharge temperature sensor 
Error Display Dual 8 Display = F5 
LED = Cooling LED-pause 3 seconds and blink 5 times 
Repair Method = Is it loose ? Measure the resistance value with universal meter 

Code = 20 
Malfunction = short-circuit of outdoor condenser temperature sensor 
Error Display Dual 8 Display = F4 
LED = Cooling LED-pause 3 seconds and blink 18 times 
Repair Method = Is it loose ? Measure the resistance value with universal meter 

Code = 21 
Malfunction = Overheat of carbon fin 
Error Display Dual 8 Display = P8 
LED = Heating LED-pause 3 seconds and blink 19 times 
Repair Method = Is outdoor ambient temperature is too high ? Is radiator mounted correctly ?
 
Code = 22 
Malfunction = DC over current 
Error Display Dual 8 Display = UU 
LED = Heating and cooling LED blink 11 times at the same time 
Repair Method = 

Code = 23 
Malfunction = Temperature sensor malfunction of carbon fin 
Error Display Dual 8 Display = P7 
LED = Heating LED-pause 3 seconds and blink 18 times 
Repair Method = Replace outdoor main board. 

Code = 24 
Malfunction = Lack of Freon or block protection 
Error Display Dual 8 Display = F0 
LED = Cooling LED-pause 3 seconds and blink 10 times 
Repair Method = 

Code = 25 
Malfunction = DC input voltage is too high 
Error Display Dual 8 Display = PH 
LED = Cooling LED-pause 3 seconds and blink 11 times 
Repair Method = Is voltage of AC power supply normal ? 

Code = 26 
Malfunction = DC input voltage is too low 
Error Display Dual 8 Display = PL 
LED = Heating LED-pause 3 seconds and blink 21 times 
Repair Method = Is voltage of AC power supply normal ? 

Code = 27 
Malfunction = Communication malfunction Setting error. 
Error Display Dual 8 Display = E6 
LED = Running LED-pause 3 seconds and blink 6 times 
Repair Method = Is Outdoor connecting wire reliably connected ? 

Code = 28 
Malfunction = Indoor and outdoor unit abnormal 
Error Display Dual 8 Display = UA 
LED = Heating and cooling LED blink 12 times at the same time 
Repair Method = Outdoor unit is not matched with indoor unit.
Read More ->>

SANYO KHS3082+CH3082 & KHS3682+CH3682 Error Code

0 komentar
Since the indications cover various units, the corresponding parts listed below may not be  present in some models. 

Indication on Indoor unit
Alarm Code = F10
LED Clean (3) = OFF
Timer (2) = OFF
Operation (1) = Blinking
Error Code = S01
Diagnosis Contents = Room temperature sensor failure
Possible Malfunction = 1. Sensor open circuit or short circuit.
2. Contact failure at connector or open circuit at terminal crimping location (short-circuit detection only for the humidity sensor)
3. Indoor/outdoor PCboard failure.

Indication on Indoor unit
Alarm Code = F02
LED Clean (3) = OFF
Timer (2) = Blinking
Operation (1) = OFF
Error Code = S02
Diagnosis Contents = Indoor heat exchanger sensor failure
Possible Malfunction = 1. Sensor open circuit or short circuit.
2. Contact failure at connector or open circuit at terminal crimping location (short-circuit detection only for the humidity sensor)
3. Indoor/outdoor PCboard failure.

Indication on Indoor unit
Alarm Code = F13
LED Clean (3) = OFF
Timer (2) = Blinking
Operation (1) = Blinking
Error Code = S03
Diagnosis Contents = Humidity sensor failure
Possible Malfunction = 1. Sensor open circuit or short circuit.
2. Contact failure at connector or open circuit at terminal crimping location (short-circuit detection only for the humidity sensor)
3. Indoor/outdoor PCboard failure

Indication on Indoor unit
Alarm Code = F04/F12
LED Clean (3) = Blinking
Timer (2) = OFF
Operation (1) = OFF
Error Code = S04
Diagnosis Contents = Compressor temperature sensor failure
Possible Malfunction = 1. Sensor open circuit or short circuit.
2. Contact failure at connector or open circuit at terminal crimping location.
3. Outdoor PCboard failure.


Indication on Indoor unit
Alarm Code = F09/F15 to F18
LED Clean (3) = Blinking 
Timer (2) = OFF
Operation (1) = Blinking
Error Code = S05
Diagnosis Contents = Outdoor heat exchanger sensor failure
Possible Malfunction = 1. Sensor open circuit or short circuit.
2. Contact failure at connector or open circuit at terminal crimping location.
3. Outdoor PCboard failure.

Indication on Indoor unit
Alarm Code = F08/F21 to F24
LED Clean (3) = Blinking
Timer (2) = Blinking
Operation (1) = OFF
Error Code = S06
Diagnosis Contents = Outdoor air temperature sensor failure
Possible Malfunction = 1. Sensor open circuit or short circuit.
2. Contact failure at connector or open circuit at terminal crimping location.
3. Outdoor PCboard failure.

Indication on Indoor unit
Alarm Code = F27
LED Clean (3) = Blinking
Timer (2) = Blinking
Operation (1) = Blinking
Error Code = S07
Diagnosis Contents = Outdoor electric current detection failure
Possible Malfunction = Outdoor PCboard failure

Indication on Indoor unit
Alarm Code = E05
LED Clean (3) = OFF
Timer (2) = OFF
Operation (1) = ON
Error Code = E01
Diagnosis Contents = Indoor/outdoor communications failure (serial communication)
Possible Malfunction = 1. Mis-wiring
2. AC power failure
3. Blown fuse
4. Power Relay failure
5. Indoor or outdoor PCboard failure
6. Outdoor Fan Motor failure
7. Reactor failure
8. High-pressure switch failure
9. Overload relay failure
10. Magnetic Coil failure

Indication on Indoor unit
Alarm Code = P26
LED Clean (3) = OFF
Timer (2) = ON
Operation (1) = OFF
Error Code = E02
Diagnosis Contents = HIC circuit failure or Power Tr (transistor) circuit failure
Possible Malfunction = 1. HIC or power Tr failure
2. Outdoor fan does not turn
3. Instantaneous power outage
4. Service valve not opened
5. Outdoor fan blocked
6. Continuous overload operation
7. Compressor failure
8. Outdoor PCboard failure

Indication on Indoor unit
Alarm Code = F31
LED Clean (3) = 0FF
Timer (2) = ON
Operation (1) = ON
Error Code = E03
Diagnosis Contents = Outdoor unit external ROM (OTP data) failure
Possible Malfunction = External Rom data failure or PCboard failure

Indication on Indoor unit
Alarm Code = P16
LED Clean (3) = ON
Timer (2) = OFF
Operation (1) = OFF
Error Code = E04 
Diagnosis Contents = Peak current cut-off
Possible Malfunction = 1. Instantaneous power outage
2. HIC or power transistor failure
3. Outdoor PCboard failure


Indication on Indoor unit
Alarm Code = P07
LED Clean (3) = ON
Timer (2) = OFF
Operation (1) = ON
Error Code = E05
Diagnosis Contents = PAM circuit failure, Active circuit failure
Possible Malfunction = 1. Outdoor PCboard failure
2. Outdoor power supply voltage failure

Indication on Indoor unit
Alarm Code = P01
LED Clean (3) = ON
Timer (2) = ON
Operation (1) = ON
Error Code = E07
Diagnosis Contents = Indoor fan operating failure
Possible Malfunction = 1. Fan motor failure 
2. Contact failure at connector
3. Indoor PCboard failure

Indication on Indoor unit
Alarm Code = P19
LED Clean (3) = Blinking
Timer (2) = Blinking
Operation (1) = ON
Error Code = E08
Diagnosis Contents = 4-way valve switching failure, Indoor zero-cross failure
Possible Malfunction = 1. 4-way valve failure (heat pump model only)
2. Outdoor PCboard failure

Indication on Indoor unit
Alarm Code = P15
LED Clean (3) = Blinking
Timer (2) = ON
Operation (1) = Blinking
Error Code = E09
Diagnosis Contents = No-refrigerant protection
Possible Malfunction = 1. Service valve not opened
2. Shortageof refrigerant

Indication on Indoor unit
Alarm Code = P29
LED Clean (3) = Blinking
Timer (2) = ON
Operation (1) = ON
Error Code = E10
Diagnosis Contents = DC compressor drive circuit failure
Possible Malfunction = 1. Open phase
2. Outdoor PCboard failure

Indication on Indoor unit
Alarm Code = P22
LED Clean (3) = ON
Timer (2) = Blinking
Operation (1) = Blinking
Error Code = E11
Diagnosis Contents = Outdoor fan operating failure
Possible Malfunction = 1. Fan motor failure
2. Contact failure at connector
3. Outdoor PCboard failure

Indication on Indoor unit
Alarm Code = E07/P04/P05/P20/P27
LED Clean (3) = ON
Timer (2) = Blinking
Operation (1) = ON
Error Code = E12
Diagnosis Contents = Outdoor system communications failure, OLR operation, Outdoor power supply open phase and Outdoor coil freezing
Possible Malfunction = 1. Mis-wiring
2. Blown fuse
3. Powe Relay failure
4. Outdoor PCboard failure
5. Compressor failure

Indication on Indoor unit
Alarm Code = P11
LED Clean (3) = ON
Timer (2) = ON
Operation (1) = Blinking
Error Code = E13
Diagnosis Contents = Freeze-prevention activated
Possible Malfunction = 1. Indoor fan system failure
2. Shortage of refrigerant
3. Low temperature operation

Technical and Service manual please download <a href="http://us.sanyo.com/dynamic/product/Downloads/30.36KHS82%20Technical%20Service%20Manual-22308430.pdf">here</a>
Read More ->>

Monday, December 6, 2010

Sanyo KS0971 KS1271 Error Code

0 komentar
Since the indications cover various units, the corresponding parts listed below may not be present in some models.
A = OFF B = Blinking C = ON (Illuminated)

Indication on indoor unit 
Qutlet (3)  = A
Timer (2)  = A
Operation (1)  = B
Code   = S01
Diagnotice item  = Room temperature sensor failure
Diagnotics contents 
(1) Sensor open circuit or short circuit
(2) Contact failure at connector or open circuit at terminal crimping location
(short-circuit detection only for the humidity sensor)
(3) Indoor/outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = A
Timer (2)  = B
Operation (1)  = A
Code   = S02
Diagnotice item  = Indoor heat exchanger sensor failure
Diagnotics contents 
(1) Sensor open circuit or short circuit
(2) Contact failure at connector or open circuit at terminal crimping location
(short-circuit detection only for the humidity sensor)
(3) Indoor/outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = A
Timer (2)  = B
Operation (1)  = B
Code   = S03
Diagnotice item  = Humidity sensor failure
Diagnotics contents 
(1) Sensor open circuit or short circuit
(2) Contact failure at connector or open circuit at terminal crimping location
(short-circuit detection only for the humidity sensor)
(3) Indoor/outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = A
Operation (1)  = A
Code   = S04
Diagnotice item  = Compressor temperature sensor failure
Diagnotics contents 
(1) Sensor open circuit or short circuit
(2) Contact failure at connector or open circuit at terminal crimping location
(3) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = A
Operation (1)  = B
Code   = S05
Diagnotice item  = Outdoor heat exchanger sensor failure
Diagnotics contents 
(1) Sensor open circuit or short circuit
(2) Contact failure at connector or open circuit at terminal crimping location
(3) Outdoor circuit board failure


Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = B
Operation (1)  = A
Code   = S06
Diagnotice item  = Outdoor air temperature sensor failure
Diagnotics contents 
(1) Sensor open circuit or short circuit
(2) Contact failure at connector or open circuit at terminal crimping location
(3) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = B
Operation (1)  = B
Code   = S07
Diagnotice item  = Outdoor electrical current detection failure
Diagnotics contents = Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = A
Timer (2)  = A
Operation (1)  = C
Code   = E01
Diagnotice item  = Indoor/outdoor communications failure (serial communications)
Diagnotics contents 
(1) Mis-wiring (2) AC power failure (3) Blown fuse (4) Power relay failure
(5) Indoor or outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = A
Timer (2)  = C
Operation (1)  = A
Code   = E02
Diagnotice item  = • HIC circuit failure • Power Tr (transistor) circuit failure
Diagnotics contents 
(1) HIC or power Tr failure (2) Outdoor fan does not turn. (3) Instantaneous power outage
(4) Service valve not opened. (5) Outdoor fan blocked. (6) Continuous overload operation
(7) Compressor failure (8) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = A
Timer (2)  = C
Operation (1)  = C
Code   = E03
Diagnotice item  = Outdoor unit external ROM (OTP data) failure
Diagnotics contents = (1) External ROM data failure (2) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = A
Operation (1)  = A
Code   = E04
Diagnotice item  = Peak current cut-off
Diagnotics contents 
(1) Instantaneous power outage (2) HIC or power transistor failure
(3) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = A
Operation (1)  = C
Code   = E05
Diagnotice item  = .PAM circuit failure .Active circuit failure
Diagnotics contents 
(1) Outdoor circuit board failure (2) Outdoor power supply voltage failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = C
Operation (1)  = A
Code   = E06
Diagnotice item  = Compressor discharge overheat prevention activated.
Diagnotics contents 
(1) Electric expansion valve failure (2) Capillaries choked (3) Shortage of refrigerant
(4) Continuous overload operation (5) Outdoor fan does not rotate (6) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = C
Operation (1)  = C
Code   = E07
Diagnotice item  = Indoor fan operating failure
Diagnotics contents = (1) Fan motor failure (2) Contact failure at connector (3) Indoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = B
Operation (1)  = C
Code   = E08
Diagnotice item  = -4-way valve switching failure -Indoor zero-cross failure
Diagnotics contents 
(1) 4-way valve failure (heat pump model only)
(2) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = C
Operation (1)  = B
Code   = E09
Diagnotice item  = No-refrigerant protection
Diagnotics contents 
(1) Service valve not opened. (2) Shortage of refrigerant

Indication on indoor unit 
Qutlet (3)  = B
Timer (2)  = C 
Operation (1)  = C
Code   = E10
Diagnotice item  = DC compressor drive circuit failure
Diagnotics contents = (1) Open phase (2) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = B 
Operation (1)  = B
Code   = E11
Diagnotice item  = Outdoor fan operating failure
Diagnotics contents = (1) Fan motor failure (2) Contact failure at connector (3) Outdoor circuit board failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = B
Operation (1)  = C
Code   = E12
Diagnotice item  
Outdoor system communications failure.
Outdoor high-pressure SW.
OLR operation.
Outdoor power supply open phase.
Outdoor coil freezing.
Diagnotics contents 
(1) Mis-wiring (2) Blown fuse (3) Power relay failure (4) Open phase
(5) Outdoor circuit board failure (6) Compressor failure

Indication on indoor unit 
Qutlet (3)  = C
Timer (2)  = C 
Operation (1)  = B
Code   = E13
Diagnotice item  = Freeze-prevention operation activated
Diagnotics contents 
(1) Indoor fan system failure (2) Shortage of refrigerant (3) Low-temperature operation
Read More ->>
 