Display = E1
Failure = EEPROM error
Display = E2
Failure = Zero crossing detection error
Display = E3
Failure = Indoor fan error
Display = E5
Failure = Room temp sensor open or short
Display = E6
Failure = Indoor coil sensor open or short
Display = EC
Failure = Refrigerant leak detected
2. Atlantic Midwall units
Display = E1
Failure = Outdoor tube sensor fault
Display = E2
Failure = Room temp sensor open or short
Display = E3
Failure = Indoor coil sensor open or short
Display = E5
Failure = Indoor fan fault
Display = E6
Failure = EEPROM error
Display = E7
Failure = External feedback fault - Check interconnecting wiring
Display = E8
Failure = Overheat detection / defrosting
3. Inverter midwall units
Display = E0
Failure = EEPROM error
Display = E1
Failure = Indoor and outdoor communication error
Display = E2
Failure = Zero crossing detection error
Display = E3
Failure = Indoor fan error
Display = E4
Failure = Indoor room temp sensor open or short
Display = E5
Failure = Indoor coil sensor open or short
Display = EC
Failure = Refrigerant leak detected
Display = F1
Failure = Outdoor temp sensor open or short
Display = F2
Failure = Condensor coil sensor open or short
Display = F3
Failure = Compressor discharge sensor open or short
Display = F4
Failure = Outdoor EEPROM error
Display = P0
Failure = IPM malfunction or IGBT over current
Display = P1
Failure = Over or under voltage protection
Display = P2
Failure = Temperature protection of compressor top (normally short of refrigerant)
Display = P4
Failure = Inverter compressor drive error
4. Fixed speed under ceiling/cassette/ducted units
Display = E1
Failure = EEPROM error
Display = E2
Failure = Zero crossing detection error
Display = E3
Failure = Indoor fan error
Display = E5
Failure = Room temp sensor open or short
Display = E6
Failure = Indoor coil sensor open or short
Display = EC
Failure = Refrigerant leak detected
Indoor
Oper.=
Time =
Def./Fan =
Alarm = Flash
Fault = Drain pump or float switch
Oper.=
Time = Flash
Def./Fan =
Alarm =
Fault = Return air sensor open or short
Oper.= Flash
Time =
Def./Fan =
Alarm =
Fault = Indoor coil sensor open or short
Oper.= Flash
Time = Flash
Def./Fan =
Alarm =
Fault = EEPROM error
Oper.=
Time =
Def./Fan = Flash
Alarm =
Fault = Outdoor coil sensor open or short
Oper.= Flash
Time = Flash
Def./Fan = Flash
Alarm = Flash
Fault = Electrical abnormality
Oper.= Flash
Time = Flash
Def./Fan =
Alarm = Flash
Fault = Over current protection
Outdoor
LED 1 = Flash
LED2 =
LED3 =
Fault = Phase rotation/phase missing error
LED 1 =
LED2 = Flash
LED3 =
Fault = HP swith open circuit
LED 1 =
LED2 =
LED3 = Flash
Fault = Overcurrent protection
LED 1 = Flash
LED2 = Flash
LED3 =
Fault = LP switch open circuit
LED 1 = Flash
LED2 = Flash
LED3 = Flash
Fault = High temperature of compressor discharge (Short of gas)
LED 1 = On
LED2 =
LED3 = On
Fault = Normal operation
LED 1 =
LED2 = Flash
LED3 = Flash
Fault = Outdoor ambient sensor open or short
5. Inverter under ceiling/cassette/ducted units
Display = E0
Failure = Communication between indoor and outdoor
Display = E1
Failure = Phase rotation/phase missing
Display = E2
Failure = Communication error between indoor unit and master unit
Display = E4
Failure = Outdoor temp sensor error
Display = E5
Failure = Compressor discharge temp sensor
Display = E8
Failure = Outdoor unit address error
Display = E9
Failure = Power volt error
Display = H0
Failure = Communication malfunction between IR341 and 780034
Display = H1
Failure = Communication between 0537 or 9177 and 780034
Display = H2
Failure = Quantity of outdoor unit decreases
Display = H3
Failure = Quantity of outdoor unit increases
Display = H4
Failure = P6 protection detected 3 times
Display = H5
Failure = P2 detected 3 times in 30 minutes
Display = H6
Failure = P4 detected 3 times in 100 minutes
Display = H7
Failure = Indoor unit decrease error
Display = H8
Failure = Discharge pressure sensor error
Display = H9
Failure = P9 detected 3 times in 30 minutes
Display = P0
Failure = Inverter compressor top temperature protection
Display = P1
Failure = HP protection
Display = P2
Failure = LP protection
Display = P3
Failure = Inverter compressor current protection
Display = P4
Failure = Compressor discharge temp protection (short of refrigerant)
Display = P5
Failure = Outdoor condensor high temp protection
Display = P6
Failure = Inverter module protection
Display = P7
Failure = Current protection No.1 Fixed compressor
Display = P8
Failure = Current protection No.2 Fixed compressor
Display = P9
Failure = Fan motor protection
Display = L0
Failure = DC inverter module protection
Display = L1
Failure = DC supply low voltage
Display = L2
Failure = DC supply high voltage protection
Display = L4
Failure = MEC Failure
Display = L8
Failure = Frequency protection
Display = L9
Failure = Frequency protection
6. MAC Cassette units
Display = E2
Failure = Room temp sensor failure
Display = E3
Failure = Coil temp sensor failure
Display = E4
Failure = Condensor sensor failure
Display = E5
Failure = Water pump temp sensor
Display = E6
Failure = Outdoor malfunction
Display = E7
Failure = EEPROM malfunction
Display = E8
Failure = Water-level alarm
7. Package units
Display = E0
Failure = Phase rotation/phase missing
Display = E1
Failure = Outdoor coil sensor in system A
Display = E2
Failure = Outdoor coil sensor in system B
Display = E5
Failure = Indoor coil sensor in system A
Display = E6
Failure = Indoor coil sensor in system B
Display = E9
Failure = Indoor temp sensor error
Display = EA
Failure = Outdoor ambient sensor error
Display = EB
Failure = Wire controller output error
Display = P0
Failure = Overcurrent protection in system A
Display = P1
Failure = Overcurrent protection in system B
Display = P2
Failure = Overcurrent protection for outdoor fan
Display = P3
Failure = Comprehensive protection for outdoor fan
Display = P4
Failure = Protection for HP/LP or discharge temp in system A
Display = P5
Failure = Protection for HP/LP or discharge temp in system B
Display = P6
Failure = HP protection initiated inT2 evaporator stops the outdoor unit fan
Display = P7
Failure = HP protection initiated inT2 evaporator stops the outdoor unit fan and compressor
Display = P8
Failure = Protection for condenser at high temp in system A
Display = P9
Failure = Protection for condenser at high temp in system B
Display = PC
Failure = Anti-freezing protection for evaporator in system A
Display = PD
Failure = Anti-freezing protection for evaporator in system B
Display = PF
Failure = Defrosting
8. Portable units
Display = HP
Failure = HP alarm
Display = Ft
Failure = Full tray or full tank
Display = Pf
Failure = Probe failure
Display = Lt
Failure = Low temp
Display = E1
Failure = Room temp sensor
Display = E2
Failure = Evaporator temp sensor
Display = E3
Failure = Condensor temp sensor
Display = P1
Failure = Bottom tray is full
8. Water heaters (Retro fit)
Display = E1
Failure = Phase reversal/phase missing error
Display = E2
Failure = Communication error between unit and wired control or sensor damaged
Display = E3
Failure = Outlet water temp sensor error
Display = E4
Failure = Water temp sensor failure in the water tank
Display = E5
Failure = Condensor temp sensor error
Display = E6
Failure = Outdoor ambient temp sensor error
Display = E7
Failure = Sensor failure at water pump outlet
Display = E9
Failure = T8 temp sensor error
Display = Ed
Failure = Sensor failure at double pipe refrigerant outlet
Display = P1
Failure = HP protection/air in system/pump not starting/no water
Display = P2
Failure = System current protection
Display = P4
Failure = Tt HP protection
Display = P5
Failure = Condenser HP protection
Display = P8
Failure = Protection for over temp at condenser outlet
Display = P9
Failure = Anti-freezing protection
Display = Pb
Failure = Anti-freezing protection
Display = H0
Failure = Indoor and outdoor units unmatched
Swimming pooll heaters
Display = E1
Failure = Phase rotation/phase missing
Display = E2
Failure = Outdoor unit and wire controller communication error
Display = E3
Failure = Outlet water temp sensor error
Display = E4
Failure = Inlet water temp sensor error
Display = E5
Failure = Evaporator pipe temp sensor error
Display = E7
Failure = Ambient temp sensor error
Display = E9
Failure = Water flow switch error
Display = EE
Failure = Discharge pipe temp sensor error
Display = P0
Failure = Discharge pressure over-high protection
Display = P1
Failure = Low pressure protection
Display = P4
Failure = Compressor over current protection
Display = P6
Failure = Evaporator over temp protection
Display = Pb
Failure = Anti-freeze protection
Display = Pf
Failure = Discharge temp protection (too high)
Integrated water heater
Display = E0
Failure = Error of sensor T5U
Display = E1
Failure = Error of sensor T5L
Display = E2
Failure = Tank and wired controller communication error
Display = E4
Failure = Condensor pipe temp sensor error
Display = E5
Failure = Outdoor ambient temp sensor error
Display = E6
Failure = Sensor Tp error
Display = E8
Failure = Electric leakage protection
Display = LA
Failure = Ambient temp is outside of range 5° _ 43°
Display = P0
Failure = Condensor pipe temp overflow protection
Display = P2
Failure = High dicharge temp
Display = P3
Failure = Open compressor circuit protection
Display = P4
Failure = Compressor overcurrent protection
Display = P8
Failure = Open upper e-heater circuit protection
Display = P9
Failure = Upper e-heater overloaded protection
Display = Pa
Failure = Open lower e-heater circuit protection
Display = Pb
Failure = Lower e-heater overloaded protection
Commercial water heater
Display = E1
Failure = Phase rotation/phase missing
Display = E2
Failure = Communication failure between wired remote and main unit
Display = E3
Failure = Outlet water temp sensor failure
Display = E4
Failure = Water temp sensor in the water tank failure
Display = E5
Failure = Condenser temp sensor failure
Display = E6
Failure = Outdoor ambient temp sensor failure
Display = E7
Failure = Electric heating pipe temp sensor failure
Display = Ec
Failure = Water inlet temp sensor error
Display = Eb
Failure = Exhaust temp sensor error (TP temp)
Display = P0
Failure = System LP protection
Display = P1
Failure = System HP protection (deficient circulating pump/pump faulty also possible)
Display = P2
Failure = Current protection for system 2
Display = P3
Failure = Current protection for system 1
Display = P8
Failure = Protection for excessive high outlet water temp
Display = Pb
Failure = Anti-freezing protection
22 komentar:
Pel dc inverter error code L4
What should be any idea
What is a E1 alarm on a under ceiling cassette mod:Invuc-60
Thanks admin for share thia important information.
v-stilshop
Thanks for this amazing article on Limousines I was Just searching for Weston Maintenance Services and found this amazing website of yours.
Thanks Dear, Nice Article.
Best AC Under Rs. 25,000 In India
I have a sign showing E03 on a Heat pump for my pool
What does it mean?
Thanks for sharing useful information. We provide Air Condition Repair Service in Guwahati.
I'm working on a alliance spit type air conditioner model Mac-afs60 and looking error codes P7, P10 and E13
Alliance midwall split unit,36000btu,defrost light keeps flashing on display and unit goes of from there
Any help please
My Alliance midwall split unit is displaying P6,i checked all comms and power connections still nothing,what might be the problem
Cleaning and Restoration for a free inspection and quote. Not only can they work directly with insurance to form sure work is performed up to the very best industry standards, but ancillary services like temporary secure storage and waste removal assure the remainder of your belongings remain safe.
Appliance Repair Woodstock GA
इसे साझा करने के लिए धन्यवाद मैं इसे नाम रिंगटोन कैसे बनायें? खोज रहा हूं
Hi I have a problem with 60000btu on hearting but def is on led
thanks for nice content keep writing and join our gaming also.
Register 918kiss
918kiss Login Pc
918kiss Angpao
918kiss Download Link
918kiss Ori
Download 918kiss
Kiosk 918kiss
918kiss2
thanks for nice content keep writing and join our gaming also.
Malaysia Online Casino
Football Betting Malaysia
Top Online Casino Malaysia
Sportbook Malaysia
Poker Online Malaysia
Trusted Online Casino Malaysia
918kiss Malaysia
thanks for nice content keep writing and join our gaming also.
Judi Slot Online Malaysia
Game Slot Online Malaysia
Playtech Slot Malaysia
Best Online Slots Malaysia
Top Live Casino Malaysia
Malaysia Slot Casino
Online Casino Malaysia
Best Online Casino Malaysia
Trusted Online Casino Malaysia
Thanks for sharing this blog. Players can also join Scr188 to Play Live Casino Games.
Scr888 Online Casino
Scr888 Login
Scr888 Apk
Scr888 Download
Scr888 Game
Download Scr888 Online
Scr888 Download Link"
Thanks for sharing this blog. This blog really help me a lot.
Online Sports Betting Malaysia
Slots Game Online Malaysia
918kiss Malaysia
Live Casino Online Malaysia
Online Gambling Malaysia
Thanks for sharing useful information ..... DiscountsPk has been facilitating the online consumer market and brand market
شركة تنظيف بالخبر
شركة تنظيف مكيفات بالخبر
Very nice Post keep sharing it helps me a lot...Such a nice writing. The style you have narrated is simple beautiful and well authored. The quality of writing can be seen from the beginning until the end. You may like to read a beautiful blog on -
Thank You!
Mac, PC & Computer Repair Adelaide
computer repairs perth
pc repairs melbourne
I care for such information a lot. I was looking for this particular information for a long time.
See the Blogspot post.
Visit the site to play Funcity33
Post a Comment